14: Charger voltage adjustment
Parameter 2: you may choose Add or Sub to adjust charger
voltage
Parameter 3: the voltage range is from 0V to 6.4V, the default
value is 0V.
15: Inverter voltage calibration
Parameter 2: you may choose Add or Sub to calibrate inverter
voltage
Parameter 3: the voltage range is from 0V to 6.4V, the default
value is 0V.
16: reserved
17: reserved
18: Charger maximum current setting
Parameter 3:
The maximum charging current could be adjusted.
Default value is 4A for long run model and 1A for standard model.
The setting range is 0.5A~6A for long run model, and 0.5A~2A for
standard model
Note:
Any modification should be suitable to battery specifications.
If input voltage is below 200VAC, the UPS will reduce charging
current to 4A automatically even though the setting is 6A.